Brand Name : Visench
Model Number : 33-20K
Place of Origin : China
Supply Ability : 10000pcs/month
Delivery Time : 30days
Packaging Details : Carton
MOQ : 1
Frequency : 50/60Hz
Output Voltage : 220/230/240VAC
Overload Capacity : 111–125%: 10 mins, 126–150%: 1 minute
Weight : Depends on the power range
Operating Temperature : 0~40℃
Rated Capacity : 1KVA -10KVA
Battery Voltage : 24VDC/36VDC/48VDC/72VDC/96VDC
Input Voltage : 220/230/240VAC
Altitude : ≤ 1000m
Humidity : 20-90%
Protection : Overload, short circuit, over voltage, low voltage, over temperature
Battery Quantity : Internal: 8/10/12pcs, External: up to 4 strings
Online Mode : 96%
Power Range : 1-20kVA
Dimension : Depends on the power range
High Frequency Online UPS
XT Series (three-three phase)
PRODUCT FEATURES
1. Advanced DSP digital control to make the control system more stable and reliable.
2. Double transform on-line design, adopting power factor coorrection (PFC) technology, input power factor is up to 0.9
3. Output power factor is 0.9(0.8 is available optional),with higher actual load capacity to save users' investiment.
4. intelligent charging management, ±16-±20pcs(32-40pcs) batteries to select.
5. Plentiful options, USB or RS485 communication interface, SNMP card (optional), parallel board (optional).
6. ECO working mode,high efficiency and energy saving reduce users' cost.
7. Parallel redundancy function, it enables to connect 4 units in parallel, and the battery pack can be shared in parallel.
8. Four modes (three phase ,three-single phase,single-three phase, single phase)
PARAMETER XT33 60-80KVA | |||
Model | XT33 60KS | XT33 80KS | |
Rated Power | 60kVA/54kW | 80kVA/72kW | |
Input | Voltage Range | 208-478Vac 3P4W+G | |
Working Frequency Range | 45-55Hz at 50Hz/ 54-66Hz at 60Hz (self-adapting) | ||
Input Power Factor | ≥0.99 | ||
Output | Rated Voltage and Accuracy | 380/400/415Vac(1±1%) 3P4W+G | |
Output Frequency | Synchronized with input ; mains frequency ≥ maximum ±10%, output frequency is 50(±0.2%)Hz ; 50/60±0.2% (battery) | ||
Rated Current | 15A | ||
Output Power Factor | 0.9 | ||
Output Harmonic Wave | ≤2% liner ; ≤5% non-liner | ||
Crest Factor | 3: | 1 | |
Output Overload | Load≤110%: 60 mins; Load≤125%: 10 mins; Load≤150%: 1 min; Load≥150% shutdown immediately | ||
Conversion time between Mains Power and Battery | 0ms | ||
Efficiency | normal mode ≥94.5% | ||
Battery | Rated Voltage | default ±192Vdc | |
Quantity | 32-40 | ||
Charging Current | 20A max | ||
Dimension (LxWxH) mm | 865x300x960 | ||
Weight | 85.5kg | ||
Working Temperature | 0℃-40℃ | ||
Altitude | <1500m | ||
Storage | -25~55℃ | ||
Relative Humidity | 0-95% (non-condensing) |
![]() |